DC SE RANGE

 

 
  • NON MAINTAINED STATIC INVERTERS WITH D.C. OUTPUT

 

 
 
Non-maintained static relays with d.c. output
 
 

The following models of static relays supply, on mains failure, a low and direct voltage to batteries kept constantly under automatic charge. The models with higher voltage (48 and 110V) require a sophisticated energy count circuit to charge the batteries. It restores the energy drawn during emergency operation. All models can be remote controlled and can relay their operating conditions to a remote location. The models with "R" suffix are fitted with reduced-maintenance batteries, while those with the "S" suffix are fitted with long life (approx. 10 years) maintenance-free batteries.

 
Technical specifications
 
INPUT VOLTAGE - 220V 50/60 Hz
OPERATING TEMPERATURE - 0 50 C
INTERVENTION THRESHOLD - 220V - 20%
CHARGE - AUTOMATIC
BATTERIES AND EQUIPMENT - ENBLOCK
FRONT LINE INDICATIONS
- BATTERIES VOLTMETER
- MAINS PRESENCE
- CHARGE/MAINTENANCE
CHARGING TIME - 10 hours
PROTECTIONS    
- EXCESSIVE DISCHARGE
- MAINS RETURN DELAY
- MAINS FUSE
- CHARGE CIRCUIT FUSE
- USE CIRCUIT FUSE
REMOTE INDICATIONS   
- MAINS PRESENT
- FAULTY USE FUSE
- EMERGENCY OPERATION
- READY TO START
REMOTE CONTROLS - ON/OFF
 

Please note that on mains presence the static relay DOES NOT supply direct current

 

 
MOD COD VOL MLW MLD BATT S.R.D. DIM KG
S 051 R 18005 12 V 500 2 N. 1 reduced maint. 12 V - 145Ah  210 x
290 x
435
680 x
320 x
520
81
S 051 S 18006 12 V 500 1 50'  n. 2 sealed 6 V - 110Ah 210 x
290 x
435
680 x
320 x
520
83
S 042 R 18003 24 V 400 2  N. 2 reduced maint. 12 V - 50Ah 210 x
290 x
435
680 x
320 x 520
68
S 042 S 18004 24 V 400 1 45'  N. 2 sealed 12 V - 40Ah 210 x
290 x
435
680 x 320 x
520
66
S 102 R 18009 24 V 1000 2 N. 2 reduced maint. 12 V - 145Ah  210 x
290 x
435
710 x
500 x
570
128
S 102 S 18010 24 V 1000 1 50'  N. 4 sealed 6 V - 110Ah 210 x
290 x
435
710 x
500 x
570
131
S 084 R 18007 48 V 800 2  N. 4 reduced maint. 12 V - 50Ah 210 x
290 x
435
710 x
500 x
570
111
S 084 S 18008 48 V 800 1 45'  N. 4 sealed 12 V - 40Ah 210 x
290 x
495
710 x
500 x
570
102
S 204 R 18011 48 V 2000 2  N. 4 reduced maint. 12 V - 145 Ah 210 x
290 x
495
1030 x
500 x
640
226
S 204 S 18012 48 V 2000 1 50'  N. 8 sealed 6 V - 110Ah 210 x
290 x
495
1030 x
500 x
640
232
S 209 R 18013 110 V 2000 2 N. 9 reduced maint. 12 V - 50Ah  210 x
290 x
495
1030 x
500 x
640
186
S 209 S 18014 110 V 2000 1 30' N. 9 sealed 12 V - 40Ah  210 x
290 x
495
1030 x
500 x
640
177
S 509 R 18015 110 V 5000 2  N. 9 reduced maint. 12 V - 145Ah 390 x
410 x
400
390 x
410 x
400*
2 x (400 x
560 x
890)  
443
S 509 S 18016 110 V 5000 1 45'  N. 18 sealed 6 V - 110Ah 390 x
410 x
400
390 x
410 x
400*
2 x (400 x
560 x
890)   
457
 
Legend
MOD = Model BAT = Batteries
COD = Code of appliance with battery S.R.D. = Static Relay Dimensions h x l x d (mm)
VOL = Rated voltage DIM = Dimensions
h x l x d (mm)
MLW = Max. load (W) KG = Weight (Kg)
MLD = Max. load duration (h)  
= DIMENSIONS WITH SEPARATED BATTERIES ON 2 BASE PLATES  
 
 

DC SE RANGE

 
 
  • STATIC RELAYS WITH D.C. OUTPUT
  • EMERGENCY OPERATION ONLY, ENCLOSED
 

 
D.C. STATIC RELAYS
 
Non maintained static relays with d.c. output (enclosed)
 
 

New models for emergency lighting equipped with battery cabinet kit. They have been designed in compliance with CEIL 64-8, C.E.I 64-10, C.E.I 17-13/1, C.E.I 21-6 and D.P.R 547 regulations.
This range of static relays is designed to supply emergency lighting systems with low direct current (12V; 24V; 48V; 110V). They supply current only on mains failure, drawing it from the batteries.
An accurate electronic circuit allows both strong and maintenance battery recharging.
Particular attention has been placed in the design of protections. The half stationary and sealed batteries are contained in a specific compartment hermetically separated from electrical components. The result is a compact and completely safe unit.
The most powerful version is equipped with a secondary battery cabinet, of the same dimensions as the main one. Detailed instructions are provided for connections. A spacious terminal compartment allows the flexible connection of signalling circuits and the remote control.

 
Technical specifications
 
INPUT 220 20% 50/60 Hz
INTERVENTION THRESHOLD 220V - 20%
MAINS INTERVENTION TIME 1 MINUTE
INTERVENTION TIME <= 0,5 SECONDS
BATTERIES SEALED, HALF-STATIONARY
CHARGE "IU" TYPE DIN 41773"
CHARGING TIME 10 h
OUTPUT CHARGE Vmax.= 1.10 VN START
VOLTAGE Vmin.= 0.90 VN END
OVERCHARGE DISCHARGE  115%
PICKUP  150% for 1 MINUTE
200% for 5 SECONDS
PROTECTIONS
-HIGH AND LOW VOLTAGE
-FAULTY BATTERIES
-EXCESSIVE DISCHARGE
-MAINS RETURN TIME
-BATTERY BUTTON
-MAINS INPUT FUSE
-CHARGE FUSE (INSIDE)
FRONT PANEL CONTROLS
-ON/OFF
-START CHARGING CYCLE
- MAINS VOLTAGE
FRONT PANEL INDICATIONS
-BATTERY VOLTAGE
-RECHARGE CURRENT
-OUTPUT CURRENT
-READY TO START
-TRIPPED SWITCHES
-MAINS PRESENT
-CHARGE/MAINTENANCE
-BATTERIES FAULT
-READY TO START
REMOTE INDICATIONS 
-TRIPPED SWITCHES
-MAINS PRESENT
-EMERGENCY OPERATION
-STRONG CHARGE
-FAULTY BATTERY
REMOTE CONTROLS LED SUPPLY      
-ON/OFF TEST
-12W AT BATTERY VOLTAGE
 
 MOD COD ROV RP RD P2D P3D BAT  KG
S 712 S/1 18033 12V 750 W 1 400 W 300 W 2 x 6V 100 Ah 120
S 1524 S/1 18034 24V 1500W 1 800 W 600 W 4 x 6V 100 Ah 160
S 1548 S/1 18035 48V 1500W 1 800 W 600 W 4 x 12V 50 Ah 160
S 3048 S/1 18036 48V 3000W 1 1600 W 1200 W 8 x 6V 100 Ah 240
S 3110 S/1 18037 110V 3000W 1 1600 W 1200 W 9 x 12V 50 Ah 280
S 6110 S/1 18038 110V 6000W 1 3800 W 3000 W 18 x 6V 100 Ah 480
 
Legend
MOD = Model P2D = Power for 2h duration
COD = Code of appliance with battery P3D = Power for 3h duration
ROV = Rated output
voltage (V)
BAT = Batteries
RP = Rated power (W) KG = Weight (Kg)
RD = Rated duration (h)  
= DIMENSIONS WITH SEPARATED BATTERIES ON 2 BASE PLATES  
 
 MODEL BATTERY CABINET UNIT DIMENSIONS       CABINET DIMENSIONS
_ A B C D E F
S 712 S/1   1000 700 500      
S 1524 S/1   1000 700 500      
S 1548 S/1   1000 700 500      
S 3048 S/1   1000 700 500      
S 3110 S/1   1200 700 500      
S 6110 S/1 n 1 1000 700 500 1000 700 500
 


 

 

Home ] Up ] [OVA EMERGENCY LIGHTING] [ALTENBURGER] [ECLAT INVERTERS]

Send mail to anthony@eclat.co.za or mwtones@mweb.co.za with questions or comments about this web site.
Copyright 2005 ECLAT LIGHTING. Telephone: +27 11 868 3779 / +27 11 868 2578. Fax: +27 11 868 2578. Mobile: +27 82 562 9620.
Last modified: July, 2010.
COPYRIGHTS AND VARIOUS PATENTS SUBSIST IN THE PRODUCTS AND IN THE CONTENT OF THIS WEBSITE. UNAUTHORIZED DUPLICATION OF THE PRODUCTS AND OF THE CONTENT BY ANY MEANS IS STRICTLY PROHIBITED. UNAUTHORIZED DUPLICATION OF ANY PROPRIETY METHODS UTILIZED AND AS DESCRIBED IN THESE PRODUCTS AND THEIR RELATED DOCUMENTS, FOR ANY OTHER THAN OUR OWN INTENDED PURPOSES, IS STRICTLY PROHIBITED. THE CONTENT OF THIS WEBSITE, IT'S PRODUCTS AND IT'S DOCUMENTS ARE STRICTLY PRIVATE AND CONFIDENTIAL, AND SHALL UNDER NO CIRCUMSTANCES BE DISCLOSED TO ANY UNAUTHORIZED THIRD PARTIES, WITHOUT PRIOR AUTHORIZATION FROM THE WRITER. PERMISSION FOR SUCH DISCLOSURE AND/OR DUPLICATION OF THESE PRODUCTS AND THESE DOCUMENTS SHALL BE APPLIED FOR, AND CONFIRMED IN WRITING. FAILURE TO FOLLOW THE ABOVE, WILL RESULT IN CIVIL AND CRIMINAL PROSECUTION.

ALL ITEMS MARKED IN RED, ARE NOT YET VERIFIED / ARE FUTURE PROJECTS / ARE IN PROGRESS.

ALL PAGES SUBJECT TO CHANGE AND TECHNICAL ERROR.