  • MAINTAINED STATIC INVERTERS WITH D.C. OUTPUT
  • INTERVENTION TIME: ZERO
 

 

Mod.
S.A. 768 S
S.A. 2400 S
S.A. 3600 S
S.A. 2736 S

 
  D.C. STATIC INVERTERS
 
General features
 
 

The main feature of these units is that they produce a DIRECT CURRENT output both on mains presence and on mains failure. The intervention time is ZERO since the unit is connected in parallel to the batteries, mains buffer supplied. Please note that the output is always powered. These units are particularly suited for systems where no supply interruption is permitted: directional indicating systems, electric box auxiliary circuits, etc.

 

 
Technical specifications
(for general use (halogen lamps, directional indicating signs, etc.)
 
 
Input voltage - 220V 50/60 Hz
Operating temperature - 050 C
Charge - AUTOMATIC
Maintenance-free batteries - HALF STATIONARY
Front panel indications - MAINS PRESENCE
- BATTERIES VOLTMETER
- BATTERIES UNDER
- CHARGE
- FAULTY BATTERIES
Protection - EXCESSIVE DISCHARGE
- FAULTY BATTERIES
- MAINS FUSE
- CHARGE
- CIRCUIT FUSE
- USE CIRCUIT FUSE
Remote indications
(except M 768)
- Faulty batteries - Imminent discharge
 
MODEL CODE OUTPUT
VOLTAGE
MAX.
LOAD
MAX.
LOAD
DURATION
SEALED
BATTERIES
 WEIGHT
Kg.
S.A. 768 S 16001 24 V CC 200 W hours 3 n2 12V 30 Ah 60
S.A. 2400 S 16002 24 V CC 600 W hours 3 n4 6V 100 Ah 140
S.A. 3600 S 16004 24 V CC 900 W hours 3 n6 4V 150 Ah 200
S.A. 2736 S 16003 48 V CC 800 W hours 3 n8 6V 75 Ah 135
 
Static relays for scialytic lamps and auxiliary services
 

 

This family of static relays has been designed to power direct current loads, both on mains presence and on mains failure. The intervention time is zero. The output voltage is always perfectly filtered. The SA 524 and SA 1024 models are especially designed to power scialytic lamps installed in operating rooms; on mains presence, they can operate even with faulty batteries. They are suitable to power any other kind of load, such as safety lighting systems. The SA. 1048 and SA. 1110 models are designed to power auxiliary circuits and maintained safety lighting systems. Particular attention has been placed in the design of filter circuits and protections. The batteries are contained in a box hermetically separated from the electronic components. The result is a compact and completely safe unit. A terminal compartment allows the flexible connection of power and signalling circuits and the remote control. A small power source (10W) is available for the supply of remote indication LED's. A second output, supplying only emergency power (mains failure), is available on request.

To power scialytic lamps (in compliance with C.E.I 64-4, C.E.I 64-8, C.E.I 64-10, C.E.I 17-13/1, C.E.I 21-6 and D.P.R 547 regulations)

 

 
MODEL CODE
appl. with
battery
RATED
VOLTAGE
RATED
POWER
DURATION BATTERIES WEIGHT (Kg) 
S.A. 524 S/3 16005 24 V CC 500 W hours 3 n2 6V 75 Ah 145
S.A. 1024 S/1 16006 24 V CC 1000 W hours 1 n4 6V 75 Ah 160
S.A. 1024 S/3 16007 24 V CC 1000 W hours 3 n6 4V 150 Ah 200
 
 

To power cabin auxiliary services (in compliance with C.E.I 64-8, C.E.I 64-10, C.E.I 17-13/1, C.E.I 21-6 and D.P.R 547 Regulations)

 

 
MODEL CODE
appl. with
battery
RATED
VOLTAGE
RATED
POWER
DURATION BATTERIES WEIGHT (Kg) 
S.A. 1048
S/1
16008 48 V CC 1000 W hours 1 n4 12V 37 Ah 150
S.A. 1110
S/1
16009 110 V CC 1000 W hours 1 n9 12V 25 Ah 180
 
Common electrical specifications
 
INPUT - 220V 20%
INTERVENTION THRESHOLD - 220 - 20
INTERVENTION TIME - ZERO
MAINS RETURN TIME - 1 MINUTE
BATTERIES - SEALED HALF STATIONARY
CHARGE - "IU" TYPE DIN 41773
CHARGING TIME - 6h SA 524 and SA 1024*
- 12h SA 1048 and SA 1110
- * al 90% Pn.
VOLTAGE OUTPUT 1,13 VN (rated voltage) end of charge / 0,90 VN end of discharge
FULL LOAD RIPPLE - 1% RMS
OVERCHARGE - 115% for 6h
PICKUP - 150% for 1'' / 200% for 5''
PROTECTIONS
- HIGH AND LOW VOLTAGE
- OUT
- OFF
- BALANCE BATTERIES
- FAULTY BATTERIES
- HIGH INSIDE TEMPERATURE
- EXCESSIVE RIPPLE
- MAINS RETURN TIME
- BATTERY BUTTON
- OUTPUT BUTTON
- MAINS INPUT FUSE
FRONT PANEL CONTROLS
- ON/OFF
- TEST
- CHARGE CYCLE START
FRONT PANEL INDICATIONS

- MAINS VOLTAGE

- BATTERY VOLTAGE

- CHARGE CURRENT

- OUTPUT CURRENT

- ON

- TRIPPED SWITCHES

- MAINS PRESENT

- CHARGE/MAINTENANCE

- BATTERY FAULT

REMOTE INDICATIONS
- ON
- TRIPPED SWITCHES
- MAINS PRESENT
- EMERGENCY OPERATION
- STRONG CHARGE
- FAULTY BATTERIES
REMOTE CONTROLS
- TEST
- ON/OFF
LED POWER SUPPLY - 12W BATTERY VOLTAGE
 
MODEL A B C D E F
S.A. 768 S 210 290 435 680 320 520
S.A. 2400 S 210 290 495 710 500 570
S.A. 3600 S 415 395 390 1235 400 540
S.A. 2736 415 395 390 1235 500 640
 
MODEL A B C
S.A. 524 S/3 700 1000 500
S.A. 1024 S/1 700 1000 500
S.A. 1024 S/3 700 1000 500
S.A. 1048 S/1 700 1000 500
S.A. 1110 S/1 700 1000 500
 

 

 

Home ] Up ] [OVA EMERGENCY LIGHTING] [ALTENBURGER] [ECLAT INVERTERS]

Send mail to anthony@eclat.co.za or mwtones@mweb.co.za with questions or comments about this web site.
Copyright 2005 ECLAT LIGHTING. Telephone: +27 11 868 3779 / +27 11 868 2578. Fax: +27 11 868 2578. Mobile: +27 82 562 9620.
Last modified: July, 2010.
COPYRIGHTS AND VARIOUS PATENTS SUBSIST IN THE PRODUCTS AND IN THE CONTENT OF THIS WEBSITE. UNAUTHORIZED DUPLICATION OF THE PRODUCTS AND OF THE CONTENT BY ANY MEANS IS STRICTLY PROHIBITED. UNAUTHORIZED DUPLICATION OF ANY PROPRIETY METHODS UTILIZED AND AS DESCRIBED IN THESE PRODUCTS AND THEIR RELATED DOCUMENTS, FOR ANY OTHER THAN OUR OWN INTENDED PURPOSES, IS STRICTLY PROHIBITED. THE CONTENT OF THIS WEBSITE, IT'S PRODUCTS AND IT'S DOCUMENTS ARE STRICTLY PRIVATE AND CONFIDENTIAL, AND SHALL UNDER NO CIRCUMSTANCES BE DISCLOSED TO ANY UNAUTHORIZED THIRD PARTIES, WITHOUT PRIOR AUTHORIZATION FROM THE WRITER. PERMISSION FOR SUCH DISCLOSURE AND/OR DUPLICATION OF THESE PRODUCTS AND THESE DOCUMENTS SHALL BE APPLIED FOR, AND CONFIRMED IN WRITING. FAILURE TO FOLLOW THE ABOVE, WILL RESULT IN CIVIL AND CRIMINAL PROSECUTION.

ALL ITEMS MARKED IN RED, ARE NOT YET VERIFIED / ARE FUTURE PROJECTS / ARE IN PROGRESS.

ALL PAGES SUBJECT TO CHANGE AND TECHNICAL ERROR.