INVERTER 103 B INVERTER 203 C INVERTER 303 D INVERTER 104 B NM INVERTER 104 B M INVERTER 204 C INVERTER 304 D INVERTER 105 D INVERTER 205 D INVERTER 305 D INVERTER 105 DL INVERTER 205 DL INVERTER 105 D2X INVERTER 105 DS INVERTER 105 P INVERTER 205 P INVERTER 305 P INVERTER 105 PL INVERTER 205 PL INVERTER 105 P2X INVERTER 105 PS INVERTER 106 D INVERTER 106 DL INVERTER 106 P INVERTER 106 PL INVERTER 108 D INVERTER 108 DL INVERTER 112 D INVERTER 112 DL INVERTER 112 P INVERTER 112 PL INVERTER 116 D INVERTER 116 DL INVERTER 116 P INVERTER 116 PL INVERTER 116 P ESU T INVERTER 216 P ESU T INVERTER 106 F INVERTER 112 F INVERTER 124 F INVERTER 148 F INVERTER 1110 F INVERTER 1220 F INVERTER 106 A INVERTER 112 A INVERTER 124 A INVERTER 148 A INVERTER 1110 A INVERTER 1220 A SELF DIAGNOSTIC (SDS) SUB STATIONS (ESU) VALID COMBINATIONS 1 VALID COMBINATIONS 2 CALCULATOR WIRING DIAGRAMS CENTRAL BATTERY (CBS)

      [Under Construction]WE ARE PROUD TO PRESENT TO YOU, MORE THAN 280 QUALITY PRODUCTS. WE HOPE YOU ENJOY YOUR VISIT. ANY QUESTIONS PERTAINING TO THIS WEBSITE OR THE PRODUCTS SHOWN, CAN BE SENT TO anthony@eclat.co.za or mwtones@mweb.co.za PLEASE INCLUDE YOUR CONTACT DETAILS.

Home
Up

Hit Counter

 

ÉCLAT INVERTER 303D M

 

The éCLAT 303 D M (3 = 3 Hour 03 = 3 Cell D = NiCad Battery M = Maintained) Inverter is a Small but robust Inverter which operates in the Maintained or Non-Maintained Mode. The current consumption is in the order of 1.4A DC and is suitable for operation off 3 - 6 pieces NiCad 4.0 - 4.4Ah Cells, offering a Duration of 3 Hour, and is suitable for operating 4W - 26W Fluorescent Lamps. Light Output is dependent on the Lamp in use. A 4W Lamp will run at 98% Light Output. (See VALID COMBINATIONS)

 

ÉCLAT INVERTER STANDARD FEATURES: -
 

Constant Light Output over entire Emergency Duration, except for the last few minutes - approximately 5 minutes. (Light Output Test Reports are available.)
Mains Presence / Charge Indicating LED.

Supplied Complete with Colour Coded Wires for faster installation.
Robust, Mill Finish Extruded Aluminium Housing.
Low Profile: 31mm x 40mm x 165mm. H x W x L. (303 D.)
Quality Electronic Components.
Glass Fibre Printed Circuit Board (PCB.)
Solder Mask is a Feature on all Inverters, which assists in preventing Short Circuits and resultant Inverter failure in damp, corrosive or wet environments.
Battery Low Voltage Cut-off Protection.
Battery Over Voltage Charge Protection.
In the Case of Lead Acid Batteries, the Charger Shuts off, until Battery requires topping up.
Mains Voltage Surge Protection.
Nominal Mains Input Voltage 230V A.C. 50 Hz ± 10%.
Failure Rate of less than 0.65%.
Design Life of 10 Years.
Inspection and Test Procedures are carried out TWICE on EACH and EVERY Inverter to ensure it’s Functionality. Full Test and Inspection procedure is available.
Light Output Tests (under a controlled environment) are carried out on a regular basis, to ensure that all Inverters conform to the set requirements.
One Type of Inverter is all that is required, to cater for all Types of Standard Control Gear, be this: -
Switched Start, Semi-Resonant, Rapid Start, Electronic, Dimmable Electronic (from any Manufacturer.) Please inquire for suitable Wiring Diagrams.

ÉCLAT INVERTER ADDITIONAL FEATURES: -
 

Inverters can be Resin Cast for Rugged Environments.
Can be Combined with a Suitable Battery within a Single Housing.
Data / Specification Sheets are available for each Inverter (except for the new products) should You require.
Can be combined with the ÉCLAT Self Diagnostic System (SDS) to allow for periodic Functional and Duration Tests. (See SDS.)

 

ADVANTAGES OF ÉCLAT INVERTERS: -
 

Not limited to a specific number of cells for a given Inverter.
Light output remains constant over the entire Duration Period, irrespective of the lamp wattage, and irrespective of the Standard Control Gear used. (Will not run into a standard 2-pin lamp, the use of which, is contrary to International Regulations.)
Not limited to a specific Ampere Hour rating of Ni-Cad Cells for a given Inverter.
Simple wiring of Inverters.
High quality Glass Fibre Printed Circuit Board, including a Solder Mask to resist moisture and resultant short circuiting.
Smallest profile for currently available Inverters, 31mm high x 40 mm wide. Standard length 165mm.
Proven design – has now been produced for 15 years, with ongoing refinement and improvements to the initial design.
The Inverter can operate in the Maintained and Non-Maintained Modes.
High Frequency, High Voltage Output, allowing for greater efficiency and smaller physical size.
Capable of running more than one lamp in the Maintained and Non-Maintained Modes. (See 303 D2X Series.)
Lightweight 210 Grams.
Economical. Current consumption under Normal Charging Conditions is a modest 100mA. (0.100 Amp.)
Low Voltage Shutoff, to protect against deep discharge of the Battery Pack.
Mains Voltage Tolerance is ± 10% at 230 V AC, 50/60 Hz.
Simply put, good quality, reliable, and economically priced.
Suitably suppressed against causing mains interference (EMI.)
The 303 D M, Maintained Inverters are identical in performance to the 103 B M and 203 C M Inverters (See INVERTER 103 B M , See INVERTER 203 C M), and are based on the same Inverter Design Principals, and therefore are of the same quality and reliability.

 

DIMENSIONS (mm) AND WEIGHTS (KG)

CODE

LENGTH

WIDTH

HEIGHT

WEIGHT

40095

165

40

31

0.215

         

LENGTH IS OVERALL LENGTH. FOR FIXING CENTRES, SUBTRACT 15mm ON OPEN UNIT, AND SUBTRACT 8mm ON HOUSED UNIT.

ÉCLAT tm 303 D M Inverter Specifications (Typical.)

ITEM NO:

DETAILS

VALUES

QTY

UNIT PRICE

1

FLUORESCENT INVERTER 303 D M.      

2

ÉCLAT CODE 40095.    

3

Mains Input Voltage. 190-260 V. AC. 50Hz.    

4

Mode Of Operation. Maintained.    

5

Battery Charge Current Maximum. 100 mA.    

6

Charger Type. Constant Current.    

7

Battery Shut off Voltage (3 Cell 4.4 Ah Battery Pack). 2.7 Volts. DC.    

8

Number of Battery Cells Required (4.4Ah.) 3-6.    

9

Battery Discharge Current. 1.4 A. DC.    

10

Inverter Efficiency. 85%.    

11

Power Delivered To Tube (Battery Voltage=3.3V DC). 3.92 Watts.    

12

Inverter Type. Flyback Switch Mode.    

13

Output Frequency. 2 MHz.    

14

Maximum Operating Temperature Shutoff. 55°C.    

15

Housed In Extruded Anodized Aluminium Housing.      
  Passive Plated End Caps, Screwed In Place.      
  Supplied Complete With Colour Coded Wires.      

16

Length. 165mm.    
  Width. 40mm.    
  Height. 31mm.    

17

Durability Subject to Environmental Conditions. Design Life, 10 Years.    

18

All Details Included On Printed Circuit Board.      

19

Serial Number Included On Printed Circuit Board.      

20

Delivery Time (From Date Of Order). 4 Weeks.    

21

Guarantee Period. 12 Months. Walk In.

Ea.

 

   

 

 

 

Home ] Up ] [OVA EMERGENCY LIGHTING] [ALTENBURGER] [ECLAT INVERTERS]

Send mail to anthony@eclat.co.za or mwtones@mweb.co.za with questions or comments about this web site.
Copyright © 2005 ECLAT LIGHTING. Telephone: +27 11 868 3779 / +27 11 868 2578. Fax: +27 11 868 2578. Mobile: +27 82 562 9620.
Last modified: July, 2010.
COPYRIGHTS © AND VARIOUS PATENTS SUBSIST IN THE PRODUCTS AND IN THE CONTENT OF THIS WEBSITE. UNAUTHORIZED DUPLICATION OF THE PRODUCTS AND OF THE CONTENT BY ANY MEANS IS STRICTLY PROHIBITED. UNAUTHORIZED DUPLICATION OF ANY PROPRIETY METHODS UTILIZED AND AS DESCRIBED IN THESE PRODUCTS AND THEIR RELATED DOCUMENTS, FOR ANY OTHER THAN OUR OWN INTENDED PURPOSES, IS STRICTLY PROHIBITED. THE CONTENT OF THIS WEBSITE, IT'S PRODUCTS AND IT'S DOCUMENTS ARE STRICTLY PRIVATE AND CONFIDENTIAL, AND SHALL UNDER NO CIRCUMSTANCES BE DISCLOSED TO ANY UNAUTHORIZED THIRD PARTIES, WITHOUT PRIOR AUTHORIZATION FROM THE WRITER. PERMISSION FOR SUCH DISCLOSURE AND/OR DUPLICATION OF THESE PRODUCTS AND THESE DOCUMENTS SHALL BE APPLIED FOR, AND CONFIRMED IN WRITING. FAILURE TO FOLLOW THE ABOVE, WILL RESULT IN CIVIL AND CRIMINAL PROSECUTION.

ALL ITEMS MARKED IN RED, ARE NOT YET VERIFIED / ARE FUTURE PROJECTS / ARE IN PROGRESS.

ALL PAGES SUBJECT TO CHANGE AND TECHNICAL ERROR.